Installation Conditions RFQ Checklist for Rack, Wall-Mount and Cabinet ESS
A distributor is asked whether a wall-mounted pack can hang on a garage stud wall. An EPC is asked whether a 100kW / 215kWh-class cabinet “just needs a concrete pad.” A datacentre buyer asks whether a 19-inch module will slide into an existing cabinet of unknown depth. These are installation-condition questions. They belong in the RFQ, together with a request for the pre-delivery mechanical drawings.
This page is a site-fit procurement checklist. It tells the buyer what to measure, photograph and write down so a supplier can confirm whether a stated configuration is even a candidate. It is not a construction guide: it does not prescribe anchors, torque, trench design, or a single fire or service clearance. Dimensions and mass vary by model. Any clearance that matters is the one on the approved drawing and, where a code applies, the one required by the authority having jurisdiction — not a number invented here.
LJY Energy is a China-based LiFePO4 battery supplier and OEM/ODM coordinator. Project fit is confirmed against your site data, the formal quotation and the approved drawing.
1. What “installation conditions” means on an RFQ
Fact (live LJY pages, 2026-11-17):
- The rack-mount ESS selection guide already tells buyers to list cabinet depth, U-height and cable-exit constraints in the RFQ.
- The 51.2V 314Ah floor cabinet tells buyers to confirm floor load capacity and says exact dimensions are confirmed in the quotation drawing.
- The C&I 100kW / 215kWh-class cabinet says outdoor cabinets in this class weigh multiple tonnes and need a concrete pad, cable trenching and maintenance clearance — confirmed in project drawings.
- The outdoor IP65-class wall-mounted page says to mount on a load-bearing wall, check the bracket and anchor rating against the unit weight (confirmed per design), install in shade with airflow, and treat IP65 as a dust and water-jet rating, not a heat rating.
Inference (procurement practice): suppliers cannot honestly “confirm it will fit” if the RFQ only names a voltage and an ampere-hour class. The missing inputs are almost always access path, residual structure, environment, and the document list the destination market will ask for.
2. Site data to collect before you send the RFQ
Have a competent person on the buyer’s side take the measurements. Record units (mm or m) and the date. Photographs with a tape or a known door width in the frame are useful attachments.
2.1 Access path (all form factors)
- Smallest door, corridor and turning point on the route from the unloading bay to the final position (width, height, any threshold or ramp).
- Lift or crane limits, if used: cabin size, rated load, and any building rule on moving batteries.
- Packed-crate limit you can actually receive, if you already know it. Packed size is requested on the drawings checklist; this RFQ supplies the site limit to compare it with.
2.2 19-inch rack modules
Fact (IEC 60297-3-100:2008): a “19-inch” front panel belongs to the 482.6 mm series, and 1U = 44.45 mm. A 3U envelope is 133.35 mm and a 4U envelope is 177.80 mm in that table. Usable rail depth and residual load are not fixed by this standard.
Collect and attach:
- Cabinet or open-frame maker and model, if known.
- Usable U height still free, and whether you need 3U-class or 4U-class space (the live 51.2V rack-mount page describes 3U for the 100Ah class and 4U for the 200Ah class as a typical series description — confirm the actual U on the project drawing).
- Depth from front mounting face to the first obstruction (door, cable tray, rear rail, wall).
- Cable exit: front, rear, left or right; any existing gland plate.
- Residual load rating of the rails or tray, taken from the cabinet or rack manufacturer, not guessed from a battery brochure.
- Whether the cabinet is indoor only. The live rack page lists IP20 as a typical indoor-rack value; a different enclosure, if required, is a project confirmation, not a default.
The typical-class size band currently published on that rack page (approximately 442–483 × 460–540 × 136–175 mm, approximately 43–50 kg) is a class orientation, not a site-fit certificate. Compare your cabinet with the approved module drawing.
2.3 Wall-mounted packs
- Indoor or outdoor mounting location; sun, dust, salt air, and whether a shade structure already exists.
- Wall construction (for example concrete, masonry, or framed studs) and who on the buyer’s side will confirm that the wall can carry the project mass, including the bracket.
- Available wall area and any window, pipe or meter that the outline must avoid.
- The IP code you want stated, if any, as a requirement to be confirmed — not as a claim copied from a product title.
- Indoor wall pages (100Ah, 200Ah) and the outdoor enclosure option are different drawings. Say which one you are asking about.
Buyer question D-0017 in LJY’s recorded demand file already asks about IP rating and heat derating for outdoor GCC-type installs (IP65 vs IP21, high ambient). That is a real RFQ subject. The outdoor product page states that IP65 does not make direct sun safe and that derating, if any, is confirmed per project. This checklist does not publish a temperature-performance figure.
2.4 Floor-standing and C&I cabinets
- Finished floor or pad outline, levelness notes if you already have a survey, and who will confirm floor or pad capacity against the drawing mass (including any bumpers or doors).
- For wheeled cabinets: whether casters are only for positioning. The live 314Ah cabinet page says to lock or remove casters and secure the unit after placement; exact mass is not a frozen catalogue number (the page uses an approximate “≈100+ kg” handling remark and points to the quotation drawing).
- For outdoor C&I cabinets: vehicle access, crane or forklift reach, cable-trench routes, drainage, fencing, and whether a pad design already exists. The live C&I page describes a multi-tonne class and says pad, trenching and maintenance clearance are confirmed in project drawings — it does not publish a pad thickness or a clearance in millimetres, and neither does this article.
- Indoor vs outdoor, dust and water exposure, and any IP code you want confirmed for the enclosure.
3. Environment and ingress protection — ask a precise question
Fact (IEC 60529, as summarised in standard IP tables): an IP code classifies protection against access to hazardous parts, solid objects, and water, using defined test methods. In those tables:
- IP20 — first digit 2: solid objects 12.5 mm and greater / finger access; second digit 0: no water protection stated.
- IP54 — dust-protected (not dust-tight) and protected against splashing water.
- IP65 — dust-tight and protected against water jets.
An IP code is not a rating for heat, UV, or salt fog, and it is not a product certificate by itself. The live outdoor wall page already states that IP65 is about dust and water jets, not heat, and that the rating of a build is confirmed per project. The C&I cabinet page treats “IP54/IP55-class” as a market reference, also confirmed per project.
On the RFQ, write the environment you actually have (indoor plant room, shaded façade, unsheltered yard, dusty workshop) and the IP code you want confirmed and marked, if you have one. Do not treat a product-page option as already proven for your serial numbers.
4. Why this page will not give a single safety distance
Buyers often ask for “the” clearance behind a cabinet or “the” fire setback. That question has no honest one-line answer on a multi-form-factor supplier site.
Fact (other manufacturer, labelled as such): the Pylontech US2000C installation manual (manufacturer PDF, opened 2026-11-17) states that model’s own size as 440 × 410 × 89 mm and mass as 22.5 kg, and it tells installers of that product to keep more than 2 meters from a heat source and more than 0.5 meters from an inverter air outlet. Those figures are Pylontech’s instructions for US2000C. They are not LJY clearances and must not be copied onto another model.
Fact (codes vary): some jurisdictions adopt installation rules for stationary energy storage, for example NFPA 855 in parts of the United States, and require plans to be submitted to the authority having jurisdiction, with the system installed to the manufacturer’s instructions and listing. Editions, amendments and exceptions differ, and local adoption can lag a newly published edition. This page does not reproduce any setback table and does not offer a global millimetre or metre promise.
Procurement action: ask the supplier to put every service, ventilation and door-swing dimension that they require on the approved drawing. Ask your designer or AHJ which destination documents apply. Compare those two sources. If they conflict, resolve it in writing before production — not on the installation day.
5. RFQ table (attach with photographs)
| Field | Buyer entry | Why it matters |
|---|---|---|
| Form factor | rack / indoor wall / outdoor wall / floor cabinet / C&I cabinet | Stops a 19-inch module being quoted for a wall bay, or the reverse |
| Electrical class requested | e.g. 51.2V 100Ah, 200Ah, 314Ah class; or 100kW/215kWh class | Class only — final build is confirmed on the quotation |
| Inverter or PCS | brand, model, firmware if known | Protocol is a separate confirmation; still useful context |
| Access path limits | door / corridor / lift, mm and kg if known | Compared with packed outline and packed mass |
| Rack conditions (if rack) | free U, rail depth, exit side, residual rail load source | 1U = 44.45 mm is the U increment, not the module depth |
| Wall conditions (if wall) | indoor/outdoor, wall type, who confirms load, shade | Mass and bracket come from the project drawing |
| Floor or pad (if cabinet) | outline, who confirms load, crane or forklift notes | Multi-tonne C&I class is confirmed in drawings, not guessed |
| Environment | min/max ambient if known, dust, water, sun | IP and thermal behaviour are confirmed per project |
| IP code requested, if any | e.g. IP20 / IP54 / IP65 as a confirmation request | IEC 60529 meaning only; not a certificate claim |
| Destination country and any known permit list | Document scope confirmed per model and market | |
| Inquiry code | ESS-Storage-RFQ (state in the message that this is a site-fit / installation-conditions RFQ) |
Send the table through the contact form. Use the existing inquiry code ESS-Storage-RFQ and state in the message that this is a site-fit / installation-conditions request. This page does not state price, MOQ, stock, lead time or certifications.
6. Related LJY pages
- Pre-delivery mechanical drawings checklist
- Mechanical site-acceptance checklist
- Rack-mount ESS selection guide
- Product hubs: 51.2V rack-mount, 48V 200Ah rack-mount, 314Ah floor cabinet, C&I 100kW/215kWh-class cabinet, outdoor IP65-class wall-mount, HV rack cluster
FAQ
Can you tell me a standard aisle width that works for every cabinet?
No. If a service or door-swing dimension is required, it belongs on the approved drawing for that model. This page will not invent a shared safety distance.
Is “19-inch 3U” enough for my cabinet shop drawing?
No. IEC 60297-3-100 fixes the 482.6 mm / 1U system. Module depth, protrusions and mass still have to come from the module drawing.
Does IP65 mean the wall unit can sit in full sun?
No. The live outdoor wall page already says IP65 is not a heat rating and that units should be installed in shade with airflow. High-temperature performance is not published as a verified LJY figure on that page.
Who confirms that my floor or wall can carry the unit?
A competent person on the buyer’s side, using the mass (and centre of gravity, if provided) from the approved drawing. A supplier website cannot certify your building.