Product Overview
If you are looking for a lithium battery for a UPS, the first thing to pin down is not capacity — it is voltage. Search results for “server rack battery” and “data center backup battery” mix two different product families that happen to share a 19-inch rack: low-voltage rack modules built for a 48V-class battery bus, and high-voltage battery strings built for the several-hundred-volt DC bus of a mid- or large-size UPS. They are not interchangeable, and choosing the wrong layer is the most common sizing mistake in lead-acid-to-lithium UPS conversions.
LJY Energy supplies both layers as LiFePO4 (LFP) builds for UPS and data-center backup projects:
- Rack modules, 48V/51.2V — 19-inch modules from 100Ah (5.12kWh, 3U) up to 200Ah and 314Ah, paralleled to size. This layer fits smaller UPS units with a 48V-class battery input, telecom power, and small server rooms.
- High-voltage packs — battery strings from 192V upward (30–100Ah class) to 384V and beyond, built to the DC bus window of three-phase UPS systems in larger data rooms.
One rule applies to both layers: compatibility with a UPS is confirmed against the exact UPS brand, model and firmware before production — never assumed from a published logo list.
Two Layers: Rack Modules vs High-Voltage Packs
Layer 1 — 48V/51.2V rack modules
The low-voltage layer uses the same 19-inch rack module family as solar and telecom storage: a 51.2V (16S) LiFePO4 module with a built-in BMS, CAN/RS485 communication, and parallel expansion — add modules to add runtime. A single 100Ah module holds 5.12kWh; a rack of them covers the backup loads of a small data room, a network closet, or a telecom site. This is the layer to choose when your UPS takes a 48V-class external battery. Full module specifications are on the 51.2V rack mount LiFePO4 battery page.
Layer 2 — high-voltage packs for three-phase UPS
Larger UPS systems do not run on 48V. Their battery strings sit at a few hundred volts, so the battery has to be built as a series string with a master control unit handling pre-charge, contactors, insulation monitoring and communication with the UPS. Strings start at 192V (30–100Ah class) and run to 384V and above, sized to the UPS battery-voltage window and the required runtime. Our series building block for this layer is the high-voltage rack battery cluster; the string configuration for a UPS project is confirmed per project.
How to tell which layer you need
Read the DC battery voltage on the UPS datasheet or rating plate. If the battery input is 48V class, you are in Layer 1. If the battery string is specified in the hundreds of volts — 192V, ±192V, 384V and similar — you are in Layer 2. If the plate is unclear, send us the UPS brand and model with your enquiry and we will identify the layer before quoting anything.
Typical Configurations
| Group | Parameter | Value | Status |
|---|---|---|---|
| Electrical | Nominal voltage (rack module) | 51.2V (16S) | Typical |
| Electrical | Module capacity options | 100Ah / 200Ah / 314Ah | Typical |
| Electrical | Module energy | 5.12kWh (100Ah) / 10.24kWh (200Ah) | Typical |
| Mechanical | Form factor | 19-inch rack, 3U (100Ah class) | Typical |
| BMS | Continuous discharge (per module) | 100A | Typical |
| BMS | Communication | CAN / RS485; dry-contact alarm signalling | To be confirmed |
| Electrical | High-voltage string voltage | 192V and above, up to 384V+ | To be confirmed |
| Electrical | High-voltage string capacity | 30–100Ah class | To be confirmed |
| Durability | Cycle life (rack module) | 6,000+ cycles | Typical |
| Documents | Certifications (UL 1973, IEC 62619, UN38.3, etc.) | Availability confirmed in writing per exact model | To be confirmed |
Values marked Typical describe the standard module class. UPS-side values — string voltage, communication pairing, discharge rate against your runtime target — are fixed only in the project specification issued with the formal quotation.
UPS Compatibility Confirmation Checklist
A lithium battery does not become UPS-compatible because a brochure says so. Compatibility is the combination of the UPS model, its battery-voltage window, its charger settings, and how alarms pass between the battery BMS and the UPS. Every project goes through this checklist, and the agreed configuration is recorded in writing before production:
- UPS details. Brand, exact model, firmware version if known, and rated load (kVA/kW).
- DC bus window. The UPS battery-voltage range (minimum, nominal, maximum) — this decides the layer and the string or module count.
- Charger settings. Float and boost voltages the UPS will apply, checked against the battery’s charge limits; adjusted on the UPS side where the model allows it.
- Communication and alarms. Whether the UPS expects a CAN/RS485 protocol profile or dry-contact signals — and confirmation that low-battery, fault and shutdown alarms reach the UPS correctly. Confirmed per UPS brand and model, item by item.
- Discharge rate and runtime. UPS backup loads discharge fast. We size the string or module count from your load and target runtime, and confirm the discharge rate and duration per project.
- Protection coordination. Breaker or DC disconnect rating, pre-charge behaviour on high-voltage strings, and cabinet or rack layout.
- Pilot first. For a first pairing with a new UPS model, start with one module or string section: verify charging, discharge, SOC and alarm behaviour on your actual UPS before the balance ships. The confirmed configuration is then locked for repeat orders.
Wholesale & Project Supply
LJY Energy is a China-based LiFePO4 battery supplier and OEM/ODM coordinator. Production is carried out by partner manufacturers; we match the build to your project, confirm the specification in writing, and coordinate quality checks and export.
- Configuration: module or string size, BMS rating, communication interface (CAN / RS485 / dry contact), enclosure and terminals — confirmed in the datasheet issued with your quotation.
- Private label: logo, case colour, rating labels, manuals and carton print for your brand.
- Quality control: pre-shipment inspection items agreed per order; third-party inspection can be arranged at the buyer’s request.
- Export documents: UN38.3 test summary, SDS/MSDS and dangerous-goods (UN3480, Class 9) paperwork for the exact model shipped, coordinated per order.
- Commercial terms: MOQ, price, lead time and warranty are confirmed per order in the quotation. No public list price.
Frequently Asked Questions
Can I replace the lead-acid batteries in my existing UPS with LiFePO4?
Usually yes, if three things line up: the battery-voltage window, the charger settings, and the alarm interface. A UPS with a 48V-class battery input takes the rack modules; a UPS with a high-voltage string takes a high-voltage pack built to its window. Some UPS models need their charge profile adjusted for lithium. All three points are confirmed against your exact UPS model before we quote — send the model number first.
How do I know whether I need rack modules or a high-voltage pack?
Check the DC battery voltage on the UPS rating plate or datasheet. 48V class means rack modules; a string voltage in the hundreds of volts (192V, 384V, ±192V and similar) means a high-voltage pack. If you cannot find it, send us the UPS brand and model and we will tell you the layer.
Will the battery communicate with my UPS?
The BMS offers CAN and RS485, and dry-contact alarm signalling where the UPS uses it. Which one applies — and the protocol profile behind it — is confirmed per UPS brand, exact model and firmware. We do not publish a compatibility list and we are not on any UPS maker’s approved-battery list; the pairing is verified per project, ideally with a pilot unit on your actual UPS.
What backup runtime can I get?
Runtime comes from your load and the energy installed: a 5.12kWh module at a 2kW load is a different answer from the same module at 5kW, and UPS loads draw at high rates for short periods. Send your load (kW) and target runtime in minutes; we size the module count or string and confirm the discharge rate in the project specification.
Which certifications do the batteries carry?
Certification availability — UL 1973, IEC 62619, UN38.3 and others — is confirmed in writing for the exact model before you order. It varies by model and destination market, so we do not claim a blanket certificate list on this page. Tell us your market and we state which source holds each report.
Can I expand the backup capacity later?
On the low-voltage layer, yes: add identical modules in parallel, with the same protocol profile and BMS firmware as the installed bank — quote your original order reference so the new modules match. High-voltage strings are expanded per project design; tell us at the first order if growth is planned, so the string and control unit are sized for it.
Request a Quotation
Send your UPS brand and exact model, the DC battery voltage if you have it, your load (kW) and target runtime, the quantity, and your destination market. We confirm the layer, the configuration and the document package in writing, then quote.