Telecom and 5G sites run radios, transmission and site controls from a −48V DC plant. When mains power fails, the battery carries the site until power returns or a generator arrives, often for hours, not minutes. Many sites still copy the Ah figure of an old lead-acid string. For a telecom base station battery, start from the measured DC load and the backup hours, then check the rectifier battery settings.
LJY Energy is a LiFePO4 supplier and OEM/ODM coordinator in Shenzhen; we are not a factory. We supply 19-inch 51.2V rack battery modules only, not UPS units, racks or PDUs.

Rack module data
| Cells | LiFePO4, 16S × 3.2 V |
| Nominal voltage | 51.2 V |
| Module options | 100 Ah · 5.12 kWh · 3U / 200 Ah · 10.24 kWh · 4U |
| Max. continuous current (100 Ah module) | 100 A |
| Operating voltage range | 44.8–57.6 V |
| Communication | CAN, RS485, RS232 |
| Modules in parallel (max.) | 16 |
| Charge temperature | 0–50 °C |
| Discharge temperature | −20–55 °C |
Source: LJY 51.2V rack module page.
Worked example: backup hours decide
Example: a base station draws 2 kW of measured DC load and must run 4 hours on battery. Energy: 2 kW × 4 h ÷ 0.92 ≈ 8.7 kWh, or 1.7 modules of 5.12 kWh, so the bank needs 2 modules of 100 Ah. Power: 2 kW ÷ 5.12 kW per module ≈ 0.4, far below the module limit. Here backup hours, not power, set the module count.
What to send before a proposal
- Measured DC load of the site in kW (average and peak).
- Backup hours required by the operator or tower company.
- Rectifier model and its battery settings: float and boost voltage, charge current limit, low-voltage disconnect.
- Free rack units (U), indoor or outdoor cabinet, and the site temperature range.
- BMS communication needed by the site monitoring (CAN or RS485).
Classify a remote communications site before you copy a base-station rack order
The rest of this page is written for a telecom or 5G site that already runs radios and site controls from a −48V DC plant, and that is being sized with 19-inch 51.2V rack modules against measured DC load and backup hours. Not every remote communications site is that plant. A rural ISP cabinet, a microwave hut, or an unmanned router site may instead use a 48V-class / 51.2V energy-storage pack plus an inverter, or a small 12V / 24V DC distribution board. Those are different voltage windows. The storage class and the telecom plant are not generic equivalents.
Before you send an enquiry, write down which architecture the site actually has:
- A −48V DC plant with a rectifier. Stay on this page. Send the measured DC load, backup hours, rectifier model and its battery settings, cabinet temperature range, and the BMS communication the site monitor needs. Polarity and the rectifier voltage window have to be confirmed; a 16S storage pack is not assumed to be a drop-in on every plant. The label differences are explained on 48V vs 51.2V vs −48V.
- A 48V / 51.2V storage bank feeding an inverter or charger. That is an energy-storage procurement, not a −48V plant replacement. Use the inverter maker’s battery window and charge settings, and do not describe the bank as a telecom −48V battery. LJY does not treat the two as universally interchangeable and does not certify named rectifier or inverter combinations on this insertion.
- A small DC-only remote site (for example a 12.8V or 25.6V radio or router board). Specify that voltage class separately. Do not order a 51.2V rack module as a generic “48V comms battery” for a 12V board.
Remote and unmanned sites add three acceptance items that a well-powered urban base station can hide:
- Climate. Charge and discharge temperature limits on this page are cited from the 51.2V rack module product page (charge 0–50°C, discharge −20–55°C on that source). If the cabinet can go below the charge minimum while a rectifier or solar charger is still trying to charge, say so in the RFQ. Do not assume a heated option is fitted.
- Standby and recharge. A site that sees rare grid or generator visits must have the autonomy hours and the recharge source (rectifier, generator, or solar) written down. This insertion does not invent a standard autonomy figure.
- Startup versus steady load. Use measured peak as well as average DC load if radios, fans or an inverter start together. The worked example already on this page sizes energy from load × hours; peak current still has to sit inside the module limit stated for the configuration you order.
This insertion does not create a second telecom slug, does not mix −48V plants with 48V / 51.2V storage as a general compatibility claim, and does not add industrial or medical grade language. Send the site architecture, the measured load and the backup hours on the contact page.
Request a sizing
Send the measured DC load, the backup hours and the rectifier model; we reply with a module count and a settings checklist for the rectifier. Prices and lead times only in a quotation.